Eaton Power Distribution Rack (PDR) Technical Specs

Electrical input
Nominal voltage 208Y/120 Vac
Nominal frequency (Range) 50/60 Hz (45-65 Hz)
Input conductor configuration Three-wire + neutral + ground
Input connection options
Direct connection to panel board main breakers (225A, 400A)
Connection into single or dual main lugs (800A)
Connection into single or dual main breakers (400A, 600A) – side access required
Options
Transient voltage surge suppression (TVSS) – 50 kA/ph or 100 kA/ph
Isolated ground
Eaton Energy Management System (EMS) branch circuit monitoring
Isolation barrier for dual-source inputs
Plexiglass or mesh doors
Distribution panelboards
42 circuit column – rated for 225A – maximum two (2) per side
42 circuit column – rated for 400A – maximum two (2) per side
Monitoring
Standard system-level monitoring
Non-volatile real-time clock
Meters and load profiling points:
Input 1 V12 min/max
Input 1 V23 min/max
Input 1 V31 min/max
Input 1 ACUV total time
Input 1 I1 min/max (with optional Main CTs installed)
Input 1 I2 min/max (with optional Main CTs installed)
Input 1 I3 min/max (with optional Main CTs installed)
Input 1 V12 THD max
Input 1 V23 THD max
Input 1 V31 THD max
Input 1 frequency min/max
Input 1 kVA min/max (with optional Main CTs installed)
Input 1 power factor min/max (with optional Main CTs installed)
Input 2 V12 min/max
Input 2 V23 min/max
Input 2 V31 min/max
Input 2 ACUV total time
Input 2 I1 min/max (with optional Main CTs installed)
Input 2 I2 min/max (with optional Main CTs installed)
Input 2 I3 min/max (with optional Main CTs installed)

Input 2 V12 THD max
Input 2 V23 THD max
Input 2 V31 THD max
Input 2 frequency min/max
Input 2 kVA min/max (with optional Main CTs installed)
Input 2 power factor min/max (with optional Main CTs installed)

GND I min/max
NEU I min/max

Event logging:
Input 1 AC over voltage
Input 1 AC under voltage
Input 1 under or over frequency
Input 2 AC over voltage
Input 2 AC under voltage
Input 2 under or over frequency
Building alarm 1
Building alarm 2
Building alarm 3
Building alarm 4
Input 1 overload (4 levels per phase, with optional Main CTs installed)
Input 2 overload (4 levels per phase, with optional Main CTs installed)
Input 1 phase rotation error
Input 2 phase rotation error
Configuration error
Alarm, high input 1 THD (per-phase alarm), current or voltage
Alarm, high input 2 THD (per-phase alarm), current or voltage
Alarm, neutral overload warning (per panel)
Neutral overload (per panel)
Ground current warning (per panel)
Ground current overload (per panel)
DSP, LCD and PowerXpert Gateway 1000 card firmware are user-upgradeable
Premium Eaton Branch Circuit Monitoring System (BCMS)
Individual panel monitoring
Configurable parameters:
Panel number
Panel name
Nominal input voltage
Nominal input frequency
System kVA
CTs present
L-L or L-N input setting
Main CT ratios
Calibration of input, output, ground and neutral CTs
Calibration of voltage
Breaker rating
Breaker warning level
Breaker type

Monitored parameters:
RMS: V1, V2, V3, I1, I2, I3
Average: Vavg, kW, kVA, PF
Load: Monthly kWh, yearly kWh, total kWh
Percentage: Input 1, Input 2, Input3, Input total (percent load)
Max: Vmax, Imax

Main panel board metering alarms Panel or subfeed breaker overload warning
Panel or subfeed breaker overload alarm
Panel breaker overload warning
Panel breaker overload alarm
Breaker current warning
Breaker current overload
Branch circuit or subfeed breaker monitoring—up to 42 per panel
(User can easily add panel breakers)
Configurable parameters—individual branch circuits

Breaker rating
Breaker warning level
Breaker overload level
Breaker type

Monitored parameters

Current: RMS and percentage
Average: kW, kVA, PF
Load: Monthly kWh, yearly kWh, total kWh
Max: Amperage, kW
Min: Power factor

Individual branch circuit alarms (for each breaker)

Breaker current warning
Breaker current overload

Connectivity
Optional Power Xpert Gateway PDP card
Built-in Web and SMTP server
Support for ModbusTCP, SNMP and NTP protocols
Two (2) isolated RJ-45 Ethernet ports for redundancy
Environmental and Safety
Operating temperature0ºC to 50ºC (32ºF to 122ºF)
Relative humidity5–95 percent non-condensing
Audible noise<45dBA measured 1.5m (5 ft.) from unit under normal operating conditions
EMIFCC 47, part 15 for Class A devices
Agency markingDomestic/Canadian models: UL/CSA 60950-1
Physical characteristics
Dimensions: H x W x D, in (mm) 23.5 x 78.5 x 38 (597 x 1994 x 965)