Eaton Modbus Card UPS Connectivity Device
- What is Modbus RTU?
- What is Jbus?
- How Does a Customer Set-up the Card?
- How does it connect to the network?
- What’s Two-wire and Four Wire topology mean?
- What does user-selectable termination mean?
- What’s selectable polarity resistance mean?
- Will the Modbus Card work with every BMS?
1. What is Modbus RTU?
Modbus is a protocol (or language) spoken by industrially oriented
equipment. SNMP and HTTP are examples of other protocols. RTU is an
acronym for Remote Terminal Unit. This is the binary, better performing
version of the protocol. We do not support the seldom-used/older ASCII
version.
2. What is Jbus?
Jbus is a slight variation of the Modbus standard. It is predominantly
used in Europe.
3. How Does a Customer Set-up the Card?
To set-up the card the user configures it with the included serial cable
and a PC running Hyperterminal. It’s just like configuring other
network devices; the user chooses a baud rate and a network address.
But the BMS doesn’t know about the UPS yet. To take care of this, the
Modbus card comes with a software package called Profiler. Profiler
creates a custom Modbus register map. This is a fancy way of saying that
it creates a file that tells the BMS what UPS it is and what it will be
monitoring. This is similar to installing a MIB on an NMS. The principal
difference is that the data is read-in in a more manual way (the MIB is
compiled in the case of the NMS). This is typical of the way users work
with a BMS so customers will be familiar with it. Profiler runs on
Windows.
The Modbus card slides into an existing X-slot in the UPS. The Expansion
Chassis comes with a preinstalled Modbus Card.
4. How does it connect to the network?
The Modbus card connects to the network via RS-485 through either an
isolated DB-9 port or terminal block. The terminal block allows
conventional twisted pair cabling for daisy chaining. Alternatively
RS-232 communications via a DB-9 port may be used. There’s a figure on
the datasheet that shows integration into a typical network.
5. What’s Two-wire and Four Wire topology mean?
It basically means that the daisy chaining connects together devices
with two or four wires. The important thing to remember is that we
support both so we meet the common topologies.
6. What does user-selectable termination mean?
Daisy chain networks require a proper termination (or end). Usually a
user has to purchase and install a termination resistor at the end of
the chain. The Modbus Card comes with a user-selectable termination. So
it may be placed at the end of a network and act as the termination
point. This eliminates the hassle and expense of purchasing and
installing a terminator.
7. What’s selectable polarity resistance mean?
It ensures that false data bits are not produced by idle
voltage.
8. Will the Modbus Card work with every BMS?
It should work with BMSs that support the Modbus protocol.
ИБП Eaton

- ИБП для компьютеров и рабочих станций
- ИБП Eaton Protection Station (500 - 800 BA)
- Eaton 3S (550-700 ВА)
- Eaton Ellipse ECO (500-1600BA)
- Eaton 5E (500-2000BA)
- Eaton 5S (550 - 1500ВA)
- Eaton Ellipse PRO (650-1600 ВA)
- ИБП для сетевого и серверного оборудования
- Eaton 5SC (500 - 3000ВA)
- Eaton 5P (650 – 1550 ВA)
- Eaton 5PX (1500-3000 BA)
- E Series DX (1-20 кВА)
- Eaton EX (700 - 1500 BA)
- Eaton 9SX (700-3000 ВA) – замена 9130
- Eaton 9SX (5-11 кВА) – замена 9130
- Eaton 9PX (1-3 кВА)
- Eaton 9PX (5-22 кВА)
- Eaton 9E (6-20 кВА)
- Eaton 9155 (8 - 30 кВА)
- ИБП с двойным преобразованием для ЦОД и ответственной электроники
- Eaton 9355
- BladeUPS (12 - 60 кВт)
- Eaton 93PM (30-500 kВА)
- ИБП Eaton 91PS и 93PS (8-30 / 40 кВт)
- Eaton 93E (15 - 200 кВА)
- Power Xpert 9395P (250 - 1200 кВА)
- Промышленный ИБП
- Промышленный ИБП Eaton 9PHD (30–200 кВА)
- ИБП для морских судов и платформ
- Eaton 9SX Marine (1000-3000 BA)
- Eaton 9PX Marine (1500-3000 BA)
- Eaton 9155 Marine (8-30 кВА)
- Eaton 93PS Marine (8-40 kW)
- Power distribution (PDU)
- Модули распределения нагрузки (PDU)
- Managed
- Switched
- Metered Outlet
- Metered Input
- In-Line Metered
- Basic
- Eaton HotSwap MBP
- Eaton FlexPDU
- ATS 16 & ATS 30
Related Information
|
Product Summary |
Find a Reseller |
Product Literature |
FAQs |